Recommended Lux Levels by Space

Recommended lux levels come from EN 12464-1, the European standard for indoor workplaces. Retail sales areas need 300 lx, rising to 500 lx at tills and office desks. Warehouse storage needs 100 lx, manned racking gangways 150 lx, and dispatch and packing 300 lx. These are maintained minimums: the level a space must still reach once fittings have aged.

By KELVANO Lighting EngineeringLast reviewed

Recommended lux levels come from EN 12464-1, the European standard for indoor workplaces: 300 lx for retail sales areas, 500 lx at tills and office desks, 100 lx for warehouse storage and 150 lx for manned racking gangways. These are maintained minimums, meaning the level the space must still reach after the fittings have aged. Below is the table by space, and how to turn a lux target into the lumens you need.

Lux, lumens and why the difference matters

  • Lumens (lm) are the total light a fitting gives out.
  • Lux (lx) is the light landing on a surface. One lux equals one lumen per square metre.

A fitting with plenty of lumens can still leave a shelf or desk under-lit if the light goes to the wrong place. That is why specifications are written in lux on the task, and why beam angle and spacing matter as much as output. See the beam angle guide for how optics change the light on the floor.

Values are maintained illuminance minimums from EN 12464-1. Many spaces are designed above them. Check the current edition for your project.

Space Lux (minimum) Notes Fittings
Retail
Sales area 300 lx Most stores design higher, plus accent on displays Retail store lighting
Till area 500 lx Glare limited to UGR 19 Anti-glare COB downlight
Wrapping and packing counter 500 lx
Supermarkets
Sales area and aisles 300 lx Check vertical light on shelf faces Supermarket lighting
Warehouses and industry
Storage and stock rooms 100 lx LED high bay lights
Racking gangways, manned 150 lx LED batten and linear lights
Racking gangways, unmanned 20 lx
Dispatch and packing 300 lx Warehouse lighting
Loading bays 150 lx LED tri-proof lights
Offices
Writing, reading, screen work 500 lx Glare limited to UGR 19
Filing and copying 300 lx
Reception desk 300 lx
Circulation
Corridors 100 lx Anti-glare COB downlight
Stairs 150 lx

Accent light: going above the minimum

The standard sets minimums for seeing the task. Retail and showroom lighting adds a second layer on top: accent light on products and displays, typically three to five times the surrounding level so they stand out. A store with a 500 lx floor might light a feature wall at 1,500 to 2,500 lx with track spots. See showroom lighting and retail store lighting for how the two layers work together.

From lux to lumens: a quick estimate

To estimate the total lumens a room needs:

Total lumens ≈ target lux × floor area (m²) ÷ 0.5

The 0.5 allows for light absorbed by walls and ceilings and for output lost as fittings age. Rooms with dark surfaces or high ceilings lose more; bright, low rooms lose less.

Example Target Area Estimate
Shop floor 300 lx 100 m² about 60,000 lm in total
Office 500 lx 50 m² about 50,000 lm in total
Warehouse storage 100 lx 1,000 m² about 200,000 lm in total

Divide the total by the output of one fitting to estimate how many you need, then check spacing so the light is even. This is a first estimate only. A DIALux calculation with your room dimensions, surfaces and fittings gives the real result. For old-bulb equivalents and how to turn lumens into watts at a given efficacy, see the lumens guide.

Other things the standard sets

  • UGR (glare): limits how much glare a scheme may produce. Offices and tills are typically UGR 19; many retail and circulation areas allow more.
  • Colour rendering: most workplaces need Ra 80 or higher. Retail, showrooms and fresh food benefit from Ra 90 so colours look true.
  • Uniformity: light should be even across the task area, not bright spots with dark gaps.

Get a calculated layout

Send your floor plan, ceiling height and the target levels from this table. We return the fittings, quantities and predicted lux, with a quotation within 24 hours. We can prepare a lighting layout for qualified projects.

Request a quote → · WhatsApp +86 189 9834 8092 · [email protected] · replies within business hours (GMT+8)

FAQ

Related questions

What is the difference between lux and lumens?
Lumens measure the total light a fitting gives out. Lux measures how much of that light lands on a surface: one lux is one lumen per square metre. A specification is written in lux, because what matters is the light on the floor, desk or shelf, not the light leaving the fitting.
How many lux does a shop need?
EN 12464-1 sets 300 lx as the maintained minimum for sales areas and 500 lx at tills. Most stores design above the minimum for general light and add accent light on displays.
How many lux does a warehouse need?
EN 12464-1 sets 100 lx for storage and stock rooms, 150 lx for manned gangways between racks, 150 lx for loading bays and 300 lx for dispatch and packing. Picking faces and inspection areas are usually designed higher.
How many lux does an office need?
500 lx on the task area for writing, reading and screen work, with glare limited to UGR 19. Corridors need around 100 lx.
How many lumens do I need per square metre?
As a first estimate, multiply the target lux by the floor area, then divide by about 0.5 to allow for light lost to walls, ceilings and ageing. For 300 lx over 100 m², that is 300 × 100 ÷ 0.5 = 60,000 lumens from all fittings together. A DIALux calculation gives the exact figure for your room.
Request a quotation

Have a project on the desk?
Get pricing in 24 hours.

  • Quotation within 24 hours, FOB, or DDP for the UK and EU, pricing by quantity
  • Samples are charged at USD 100–300 per piece, depending on the product and its configuration. Standard samples are ready in 7 days; samples that need new tooling are quoted with their own lead time. The sample charge is credited against your first order over USD 3,000 placed within six months.
  • Orders of around 500 units ship in 25–35 days from the deposit; larger or customised orders are confirmed on the proforma invoice.
  • IES and LDT photometric files can be measured for project specifications
  • Answered by our project team
Products of interest

We reply within 24 hours. Drawings or DIALux files: send to [email protected].